How to Size an Off-Grid Cabin Power System

Cabin power systems are usually sized from a guess, and the guess is usually a battery that is one size too small. The fix is a method, and it fits on one page: audit every load in watt-hours, decide how many sunless days the system must survive, convert that into battery capacity, and then size the solar array for your region and your worst month. This guide works the method in the open, with a full cabin example.

Published Nov 24, 2026

Step 1: audit the loads before pricing anything

Every cabin sizing mistake starts the same way: someone picks a battery size from a forum post and then discovers what their loads actually cost. The audit comes first. List everything the cabin has to run, attach a watt figure and a realistic hours-per-day figure to each, and multiply. These planning averages are the ones used across this site’s energy guides:

LoadPlanning figureDaily energy
Refrigerator (modern)~60 W average, around the clock1,440 Wh
LED lighting30 W while on150 Wh at 5 hours
Router and modem15 W, always on360 Wh
Laptop65 W while charging260 Wh at 4 hours
Television100 W while on300 Wh at 3 hours
CPAP40 W with heated humidifier320 Wh per night
Furnace blower400 W while runningvaries with the heating load

Two lines catch people out. The first is the fridge: it dominates almost every cabin budget, because it is the one load that never takes a day off. The second is the one that is not on the list at all — the power station’s own idle draw. A switched-on station spends roughly 10 to 18 W keeping its inverter and electronics awake, which is 240 to 430 Wh across a day spent powering nothing else. At cabin scale that is a real appliance, and it belongs in the audit. Where a load can run from 12 V DC instead of an AC outlet — a 12 V fridge is the classic case — it also skips the inverter’s conversion losses, roughly 10 to 15%.

Step 2: set days of autonomy

Autonomy is the number of sunless, engineless days the system has to survive on battery alone. Two days is the common planning figure for a cabin that sees regular use: it covers a stormy weekend without rationing, and each additional day costs a full day of battery capacity, so the third day is a deliberate purchase rather than a default. Multiply the daily total by the autonomy days to get the usable energy the bank has to hold. Then convert usable to nameplate: a power station delivers about 85% of its rated watt-hours in practice, so divide by 0.85. For a stationary component bank, depth of discharge does the same job — the battery sizing calculator runs that stationary version of the arithmetic.

Step 3: size the solar array by region and season

Solar sizing starts from peak sun hours, the daily total of full-strength sun your location effectively receives. As planning approximations — labeled as such, because your ridge, trees and weather will move them — this site uses 5.5 for the Southwest, 4.5 for the Southeast, 4.2 for the Midwest, 4.0 for the Northeast and 3.5 for the Pacific Northwest, with a winter derate of about 40% on top. The formula is the same one behind the runtime guide’s solar math: panel watts = daily watt-hours ÷ (peak sun hours × 0.8), where the 0.8 absorbs angle, heat and haze. Run it for your worst month, not your best: a cabin system sized on July sun is a system that goes dark in January, and the winter guide covers what the cold does to the battery half of the plan.

The worked example: a small full-time cabin

Take a modest cabin load list from the table: the fridge (1,440 Wh), lights (150 Wh), the router (360 Wh), a laptop (260 Wh) and an evening television (300 Wh) total 2,510 Wh per day. Add a 2 kWh-class station’s idle draw at 10 W — 240 Wh — and the planning total is about 2,750 Wh per day. Two days of autonomy means 5,500 usable watt-hours, which is about 6,500 Wh of nameplate capacity once the 0.85 factor is applied. That is past any single mid-size station, so this cabin is already a decision: a 240 V-class station with expansion batteries, or a component bank.

Solar for the same cabin in the Southeast: 2,750 ÷ (4.5 × 0.8) is about 764, so roughly 800 W of panels balances the budget on an average day. In winter, with peak sun hours derated to about 2.7, the same arithmetic asks for roughly 1,300 W — or the cabin accepts shorter autonomy in December and tops up from a generator on the worst weekends. Neither answer is wrong. What is wrong is discovering the gap after the panels are mounted.

Station-based or component-based at cabin scale?

Below roughly 3 to 5 kWh of daily use, a power station is hard to beat: no wiring, no panel work, a fast UPS-grade switchover, and it can come home with you in the off-season. The expandable 2 kWh units below are the usual cabin starting point — one runs the fridge-and-lights version of the worked example for a day, and extra batteries stretch the same box toward the full budget.

Prices are editorial estimates, checked against retailer listings on the date stated on the page, and change often — the links open current listings where you can verify price and availability. Some links may earn a commission at no cost to you — see the disclosure page.

Above that band, a component system — a separate charge controller, inverter and lithium iron phosphate bank — wins on cost per kilowatt-hour and on repairability: a failed controller is a part, not a product. The trade is real work: DC cable runs, fusing, grounding, and a system that stays at the cabin. Many working cabins end up hybrid in spirit even when they start simple: a station as the always-ready core, and components added when the load list outgrows it. One boundary to respect in either design: 240 V loads such as a well pump sit outside the small-station world entirely, and they push the design toward the 240 V class or a component inverter — the whole-home backup guide works through what split-phase power changes.

What this method deliberately leaves out

The audit sizes energy, not comfort. It says nothing about heating fuel, water, or the hundred other systems a cabin needs, because those are not electrical sizing questions. It also assumes the load list is stable; the cheapest capacity upgrade in any off-grid system is still a smaller fridge. Get the audit right, though, and the rest of the purchase is just choosing which box holds the numbers — the runtime guide shows how those numbers behave load by load once the system is running.

Official documentation and references

Frequently asked questions

How many watt-hours does a small cabin use per day?

A fridge-led load list lands between roughly 2,000 and 3,000 Wh per day: the fridge alone is about 1,440 Wh, and lights, network gear and devices add the rest. The worked example in this guide totals about 2,750 Wh per day once the power station’s own idle draw is included. Cabins without a fridge, or with a small DC fridge, come in well under that.

How many days of autonomy should a cabin system have?

Two days is the common planning figure. It carries the system through a stormy weekend without rationing, and each extra day costs a full additional day of battery capacity, so a third day should be a deliberate decision based on how far the cabin is from help and how often it is occupied in winter.

How much solar do I need per 1,000 Wh of daily use?

Divide by peak sun hours times 0.8. At the Southeast planning figure of 4.5 peak sun hours, that is about 280 W of panels per 1,000 Wh of daily load. Derate for winter — at about 2.7 effective peak sun hours the same 1,000 Wh needs roughly 460 W of panels to stay balanced.

Can one portable power station run a whole cabin?

At weekend scale, yes: a 2 kWh station covers a fridge, lights and network gear for about a day, and expansion batteries stretch it further. The limits are 240 V loads such as well pumps, which small stations cannot supply at any capacity, and multi-day autonomy, which pushes the design toward the 240 V class or a component bank.

Power station or components for a permanent cabin?

The crossover sits around 3 to 5 kWh of daily use. Below it, a station wins on simplicity, portability and zero wiring. Above it, a component system wins on cost per kilowatt-hour and repairability. Many cabins run a station first and add components when the load list outgrows the box.