UPS Runtime Calculator
Work out how long a battery backup will actually carry your NAS, switch and router when the power drops. Enter the battery your UPS really has and the load your gear really draws, and the calculator returns a runtime range you can plan around — not the flattering number on the box.
The estimate appears here as you type.
How the estimate works
Battery capacity is the part the box makes hardest to find, so the calculator builds it from the batteries themselves: count × volts × amp-hours gives watt-hours. A 1500 VA unit with two 12 V, 9 Ah batteries holds 216 watt-hours. From there the math is plain division — usable watt-hours divided by your load in watts gives hours — with two deductions applied first. The inverter that turns battery DC into wall-outlet AC wastes roughly 10–20% as heat, and a battery that is drained to absolute empty gives up capacity and wears out faster, so the calculator only counts the share you would actually use.
The result is a range because the last variable cannot be typed in: lead-acid batteries deliver less of their rated capacity the harder they are drained (the Peukert effect), and they lose more with age. At a light load the top of the range is realistic; at a heavy load, or with three-year-old batteries, plan on the low end. If your UPS reports its own runtime estimate over USB or the network, treat that as a cross-check — it is measuring your real batteries, which no calculator can do.
How much runtime do you actually need?
Most home outages are measured in seconds or minutes, and most home servers do not need to outlast the long ones. What they need is enough battery to finish writing, close the storage pool and shut down cleanly — five to ten minutes covers it. That shutdown does not have to be manual: NUT (Network UPS Tools) watches the UPS and tells the NAS and every other connected machine to shut down in order when the battery runs low. Size the UPS for the load first, then let the runtime number tell you whether your shutdown plan has room to spare.
Frequently asked questions
How long will a 1500 VA UPS run a NAS?
A typical 1500 VA desktop UPS carries two 12 V, 9 Ah batteries, which is 216 watt-hours before losses. After inverter losses and a sensible discharge limit, about 145 watt-hours is usable, so a NAS plus router and switch drawing 120 W runs for roughly 70 minutes on paper. Plan on 55 to 70 minutes in practice, and less as the batteries age.
Does a bigger VA rating mean longer runtime?
No. The VA rating caps how much load the UPS can carry at once; runtime comes from the battery, measured in watt-hours. Two UPS units with the same VA rating can carry very different batteries, and a small UPS with a big battery can outlast a large UPS with a small one. Check the battery count, volts and amp-hours on the spec sheet when runtime is what you care about.
Why is real runtime shorter than the headline number?
Lead-acid batteries deliver less of their rated capacity when they are drained quickly — the Peukert effect — and they lose capacity with age and cold. The inverter also wastes some energy as heat. The calculator counts inverter losses up front and shows a planning range whose low end assumes the real-world haircut, so the number you plan around is the low one.
How much runtime do I actually need?
For most home servers the job is not to keep running through the outage — it is to shut down cleanly before the battery dies. Five to ten minutes of runtime is enough for a NAS to close its files and power off, and a tool like NUT (Network UPS Tools) can trigger that shutdown automatically when the battery runs low. Longer runtime matters when you want network gear to stay up through short outages, which are the common case.